2024-03-21

IEEE 1584-2018 Arc-Flash calculation Steps [1]

 

According to IEEE 1584-2018 Guide follow 11 Steps to perform calculation of Arc-Flash Boundary (AFB) and Incident Energy (IE), as below.

Step 1Collect the system and installation data

While the data required for this study is similar to data collected for typical short-circuit and protective-device coordination studies, it goes further in that all low-voltage distribution and control equipment plus its feeders and large branch circuits must be included.

Step 2Determine the system modes of operation

In a site with a simple radial distribution system there is only one mode of operation.

Step 3Determine the bolted fault currents

Input  all  data  from  the  single-line  diagrams  and  the  data  collection  effort  into  a  short-circuit  program. Run and get the faulted currents.

Step 4Determine typical gap and enclosure size based upon system voltages and classes of equipment

Typical gaps between conductors (or bus gaps) as shown in Table 1 which also provides information on the enclosure sizes used for each voltage class.


Table 1 Classes of equipment and typical bus gaps

Equipment class

Typical bus

Gaps (mm)

Enclosure Size (H × W × D)

SI units (metric)

15 kV switchgear

152

1143 × 762 × 762 mm

15 kV MCC

152

914.4  × 914.4  × 914.4 mm

5 kV switchgear

104

914.4  × 914.4  × 914.4 mm

5 kV switchgear

104

1143  × 762  × 762 mm

5 kV MCC

104

660.4  × 660.4  × 660.4 mm

Low-voltage switchgear

32

508  × 508  × 508 mm

Shallow low-voltage

MCCs and panel boards

25

355.6  × 304.8mm  × ≤203.2 mm

Deep low-voltage MCCs

and panel boards

25

355.6  × 304.8mm  × >203.2 mm

Cable junction box

13

355.6  × 304.8 mm × ≤203.2 mm  or

355.6  × 304.8 mm × >203.2 mm

 

Step 5 Determine the equipment electrode configuration

The following electrode configurations are defined and listed according to their order of use within the incident energy model

— VCB Vertical conductors/electrodes inside a metal box/enclosure

— VCBB Vertical conductors/electrodes terminated in an insulating barrier inside a metal box/enclosure

— HCB Horizontal conductors/electrodes inside a metal box/enclosure

— VOA Vertical conductors/electrodes in open air

— HOA Horizontal conductors/electrodes in open air

Step 6 Determine the working distances

Typical working distances can be found in Table 2 based on the class of equipment.

Table 2 Classes of equipment and typical working distances

Equipment class

Working distance (mm)

15 kV switchgear

914.4

15 kV MCC

914.4

5 kV switchgear

914.4

5 kV MCC

914.4

Low-voltage switchgear

609.6

Shallow low-voltage MCCs and panelboards

457.2

Deep low-voltage MCCs and panelboards

457.2

Cable junction box

457.2

 

Step 7 Calculation of arcing current

To determine the arcing current

1.           Determine the applicable equipment electrode configuration.

2.           If the system voltage is 600 V < Voc ≤ 15 000 V, use Equation (1) to find intermediate values at 600 V, 2700 V, and 14300 V. Use Equation (2), Equation (3), Equation (4) to find the final value of the arcing current.

3.           If the system voltage is 208 V ≤ Voc ≤ 600 V, use Equation (1) to find the intermediate value (600 V only) and Equation (5) to find the final value.

Formula as below

Find intermediate valu(1)


where

I bf the bolted fault current for three-phase faults (symmetrical rms) (kA)

I arc_600 the average rms arcing current at Voc = 600 V (kA)

I arc_2700 the average rms arcing current at Voc = 2700 V (kA)

I arc_14300 the average rms arcing current at Voc =14 300 V (kA)

G the gap distance between electrodes (mm)

k1 to k10 are the coefficients provided in Table 3

lg log10

Table 3—Coefficients for Equation (1)



Find final value (600 V < Voc ≤ 15000 V)       (2)

 (3)                     (4)

 where

I arc_1 the first I arc interpolation term between 600 V and 2700 V (kA)

I arc_2 the second I arc interpolation term used when Voc > 2700 V (kA)

I arc_3 the third I arc interpolation term used when Voc is < 2700 V (kA)

Voc the open-circuit voltage (system voltage) (kV)

When 0.600 < Voc ≤ 2.7, the final value of arcing current is given as follows

I arc = I arc_3

When Voc > 2.7, the final value of arcing current is given as follows

I arc = I arc_2

Find final value (Voc ≤ 600 V)

                    (5)

where

Vocthe open-circuit voltage (kV)

Ibf the bolted fault current for three-phase faults (symmetrical rms) (kA)

Iarc the final rms arcing current at the specified Voc (kA)

Iarc_600 the rms arcing current at Voc=600 V found using Equation (1) (kA)

Step 8 Determine the arc duration

The arc duration is most commonly dependent on the operating time of a time-overcurrent protective device.

No comments:

Post a Comment

Note: Only a member of this blog may post a comment.