2024-03-21

IEEE 1584-2018 Arc-Flash calculation Steps [2]

 

Step 9 Calculate the incident energy

To determine the incident energy

1.      Determine the enclosure size correction factor.

2.      If the system voltage is 600 V < Voc ≤ 15000 V, use Equation (6), Equation (7), and Equation (8) to find intermediate values. Use Equation (10), Equation (11), Equation (12) to find the final value of the incident energy.

3.      If the system voltage is 208 V ≤ Voc ≤ 600 V, use Equation (9) to determine the final incident energy.

Formula as below

Find intermediate values        (6)

(7)

         (8)

(9)

 where

E600 is the incident energy at Voc = 600 V (J/cm2)

E2700 is the incident energy at Voc = 2700 V (J/cm2)

E14300 is the incident energy at Voc = 14 300 V (J/cm2)

E≤600 is the incident energy for Voc ≤ 600 V (J/cm2)

T the arc duration (ms)

Gthe gap distance between conductors (electrodes) (mm)

Iarc_600 the rms arcing current for 600 V (kA)

Iarc_2700 the rms arcing current for 2700 V (kA)

Iarc_14300 the rms arcing current for 14 300 V (kA)

Iarcrms arcing current for Voc ≤ 600 V [using Equation (25)] (kA)

Ibf bolted fault current for three-phase faults (symmetrical rms) (kA)

D the distance between electrodes and calorimeters (working distance) (mm)

CF correction factor for enclosure size (CF = 1 for VOA and HOA configurations)

lg log10

k1to k13 the coefficients provided in Table 4, Table 5, and Table 6.

Table 4 Coefficients for Equation (6), Equation (9), Equation (13), and Equation (16)


Table 5 Coefficients for Equation (7), Equation (14)

Table 6 Coefficients for Equation (8), Equation (15)

Find final value (600 V < Voc ≤ 15000 V)

                  (10)                (11)                  (12)

 where

E1 the first E interpolation term between 600 V and 2700 V (J/cm2)

E2 the second E interpolation term used when Voc is > 2700 V (J/cm2)

E3 the third E interpolation term used when Voc is < 2700 V (J/cm2)

When 0.600 < Voc ≤ 2.7, the final values of incident energy is given as follows

E = E3

When Voc > 2.7, the final values of incident energy is given as follows

E = E2

Find final value (Voc ≤ 600 V)

The incident energy is given as follows

E = E≤600

where

E≤600 the incident energy for Voc ≤ 600 V determined using Equation (9) solved using the arc current determined from Equation (1) and Equation (5) (J/cm2)

E the final incident energy at specified Voc (J/cm2)

Step 10 Determine the arc-flash boundary for all equipment

To determine the arc-flash boundary

1.    Determine the enclosure size correction factor

2.    If the system voltage is 600 V < Voc ≤ 15000 V, use Equation (13), Equation (14), and Equation (15) to find intermediate values. Use Equation (17), Equation (18), Equation (19) to find the final value of the arc-flash boundary.

3.    If the system voltage is 208 V ≤ Voc ≤ 600 V, use Equation (16) to determine of the final arc-flash boundary.

Formula as below

Find intermediate values

(14)

 

(15)




where

AFB600 the arc-flash boundary for Voc = 600 V (mm)

AFB2700 the arc-flash boundary for Voc = 2700 V (mm)

AFB14300 the arc-flash boundary for Voc = 14 300 V (mm)

AFB600 the arc-flash boundary for Voc ≤ 600 V (mm)

G the gap between electrodes (mm)

Iarc_600 the rms arcing current for 600 V (kA)

Iarc_2700 the rms arcing current for 2700 V (kA)

Iarc_14300 the rms arcing current for 14 300 V (kA)

Iarc the rms arcing current for Voc ≤ 600 V [obtained using Equation (5)] (kA)

Ibf the bolted fault current for three-phase faults (symmetrical rms) (kA)

CFthe correction factor for enclosure size (CF=1 for VOA and HOA configurations)

Tthe arc duration (ms)

lg log10

k1 to k13 are the coefficients provided in Table 4, Table 5, and Table 6.

Find final value (600 V < Voc ≤ 15000 V)

      (17)                                

       (18)

       (19)

 where

AFB1 the first AFB interpolation term between 600 V and 2700 V (mm)

AFB2 the second AFB interpolation term used when Voc is greater than 2700 V (mm)

AFB3 the third AFB interpolation term used when Voc is less than 2700 V (mm)

When 0.600 < Voc ≤ 2.7, the final values of arc-flash boundary are given as follows

AFB = AFB3

When Voc > 2.7, the final values of arc-flash boundary are given as follows

AFB = AFB2

Find final value (Voc ≤ 600 V)

The arc-flash boundary is given as follows

AFB = AFB≤600

where

AFB600arc-flash boundary for Voc ≤ 600V determined using Equation(16) solved using the arc current determined from Equation (1) and Equation (5) (mm)

AFBthe final arc-flash boundary at specified Voc (mm)

Step 11 Determine second arcing current

It must account for the arcing current variation. Repeat step 8, step 9, and step 10 using the reduced arcing current. It is possible that the incident energy and arc-flash boundary results obtained using the reduced arcing current are different. The final incident energy or arc-flash boundary is the higher of the two calculated values.

(20)

 where

VarCf the arcing current variation correction factor

Iarcthe final or intermediate rms arcing current(s) (kA) (see note)

Iarc_min a second rms arcing current reduced based on the variation correction factor (kA)

Voc the open-circuit voltage between 0.208 kV and 15.0 kV

k1 to  k7 the coefficients provided in Table 7

Table 7 Coefficients for Equation (20)


NOTE—The correction factor (1 – (0.5 × VarCf)) is applied as follows

208 V ≤ Voc ≤ 600 V To Iarc (final current only)

600 V < Voc ≤ 15000 V To Iarc_600, Iarc_2700, and Iarc_14300 (intermediate average arcing currents). The final Iarc value inherits the correction factor.

The “0.5” coefficient indicates that variation is applied to the average arcing current to obtain a lower-bound value arcing current.

No comments:

Post a Comment

Note: Only a member of this blog may post a comment.